DVP04PT-E2 temperature measurement module receives 4 points of platinum temperature sensors (PT100 3-WIRE 100Ω 3850 PPM/°C (DIN 43760 JIS C1604-1989)/ NI100 / PT1000 / NI1000) and converts them into 16-bit digital signals. Users can select the temperature to be displayed in Celsius (°C) or Fahrenheit (°F). Resolution of temperature in Celsius: 0.1°C and in Fahrenheit: 0.1°F. In addition, you can access the data in the module by applying FROM/TO instructions or read the average value of channels directly by using MOV instruction (Please refer to allocation of special registers D9900 ~ D9999).
Specifications:
*MPU points: 16 / 20 / 24 / 32 / 40 / 60
*Program capacity: 16k steps
*Built-in with 3 COM ports: 1 RS-232 port and 2 RS-485 ports, all are able to operate independently (Master/Slave)
*Max. I/O points: 256 input points + 16 output points, or 256 output points + 16 input points
*DVP-EX2 MPU is built in with 12-bit 4AD/2DA and offers analog/temperature modules of 14-bit resolution.
*Built-in with 8 high-speed input points (2 points for 100kHz, 6 points for 10kHz) and supports U/D, U/D Dir, A/B counting modes
*New motion control instructions: Close loop control, alignment mark, shield, immediate variable speed, S-Curve acceleration/deceleration
*Application in emerging industry: Exclusive instructions and function blocks designed for PV solar tracker
*Handy instructions for frequency inverter: For controlling the forward running, reverse running, RUN and STOP of Delta's AC motor drives
*Password protection: Password for subroutine, user ID, restriction on trial times
*Highly efficient instruction efficient instruction execution
| Update 200 I/O extension points | LD instruction | MOV instruction | DMUL instruction | DEMUL instruction |
ES2 | 1ms | 0.54us | 3.4us | 11.4us | 10.3us |
ES | 6ms | 3.8us | 18us | 150us | 55.4us |
Note | Update I/O extension module | Basic instruction | 16-bit data movement instruction | 31-bit multiplication instruction | 32-bit floating point multiplication |
Model Item | 16ES2 00_ | 24ES2 00_ | 32ES2 00_ | 40ES2 00_ | 60ES2 00_ | 20EX2 00_ | 32ES2 11T |
Power supply voltage | 100 ~ 240VAC (-15% ~ 10%), 50/60Hz + - 5% | 24VDC (-15~+20%) |
Connector | European standard removable terminal block (Pin pitch: 5mm) |
Operation | ES 200 | DVP-ES2 starts to run when the power rises to 95 ~ 100VAC and stops when the power drops to 70VAC. If the power is suddenly cut off, the MPU will continue running for 10ms. |
ES 211 | DVP-ES2 starts to run when the power rises to 20.4VDC~28.8VDC and stops when the power drops to 17.5VDC. If the power is suddenly cut off, the MPU will continue running for 10ms. |
Power supply fuse | 2A/250VAC | 2.5A / 30VDC, Polyswitch |
Power consumption | 30VA | |
DC24V current output | 500mA | / |
Power supply protection | DC24V output short circuit protection | / |
Voltage withstand | 1,500VAC (Primary-secondary), 1,500VAC (Primary-PE), 500VAC (Secondary-PE) |
Insulation resistance | > 5M Ohm at 500VDC (between all I/O points and ground) |
Noise immunity | ESD: 8KV Air Discharge EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 1KV RS: 26MHz ~ 1GHz, 10V/m |
Grounding | The diameter of grounding wire shall not be less than that of L, N terminal of the power supply. (When many PLCs are in use at the same time, please make sure every PLC is properly grounded.) |
Environment | Operation: 0°C~55°C (temperature), 50~95% (humidity), pollution degree 2 Storage: -25°C~70°C (temperature), 5~95% (humidity) |
Agency approvals | UL508 European community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC |
Vibration/shock immunity | International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) |
Weight (g) | R | 377 | 414 | 489 | 554 | 696 | 462 | / |
T | 351 | 387 | 432 | 498 | 614 | 442 | 321 |